![]() ![]() ![]() This makes sure that the coil of K2 is energized only when K3 is open and the coil of K3 is energized only when K2 is open. Additionally, they are also mechanically interlocked. Star contactor (K2) and Delta contactor (K3) are electrically interlocked using NC contacts, such that both contactors are never closed at a time. When S0 is pressed or during overload trips or the F1 fuse blown-outs, the coils of the contactor K1 and K3 de-energize and the motor stops. The NO contact of K1 is wired parallel to S1 such that the circuit remains latched until S0 is pressed.Īfter the time duration is set on the star delta timer, the K2 coil is de-energized and K3 is energized and the motor runs in the delta configuration. This will drive the motor in the star configuration. Under normal conditions (F1, F2, and F3 are healthy), when S1 is pressed, timer coil K4 will pick up and it energizes the coil of the contactor K2, and that in turn energizes the coil of line contactor K1. ![]() Figure 1A: Star delta starter power and control circuits ![]()